IDP Library - Brent Cross
Reference person: | Kristian Skeie (SINTEF) |
---|---|
Simulation report: |
Reference building
Name: | Brent Cross |
---|---|
Location: | London (UK) |
General data
Urban context: | suburban |
---|---|
Climate: | H&CD |
Building: | purpose-built |
Year of construction: | 1976 |
Year of retrofit: | 2000 |
GLA before retrofit [m²]: | 84200 |
GLA after retrofit [m²]: | 84200 |
Shopping centre size: | Very large |
Shopping centre sub-typology: | super-regional |
Food store format: | none |
Food store vending area [m²]: | 3680 |
Tenants vending area [m²]: | 80400 |
Common areas and galleries [m²]: | 13500 |
Nr of opening hours per day [h/d]: | 10.0 |
Nr of opening days per week [d/w]: | 7 |
Nr of closing days per year (because of holidays) [d/y]: | 3 |
Building features
Centre design: | enclosed |
---|---|
Shape: | 0.6 |
Orientation: | E/W |
Number of levels above ground: | 2 |
Number of underground levels: | 0.0 |
Parking location: | external multistorey carpark |
Number of parking levels: | - |
Biologically active area [%]: | 0.00% |
Perimeter
Wall structure: | masonry |
---|---|
Wall insulation location: | out |
Wall insulation material: | mineral |
Wall U-value [W/m²K]: | 0.450 |
WWR - north [%]: | 1 |
WWR - east [%]: | 1 |
WWR - south [%]: | 4 |
WWR - west [%]: | 1 |
Windows U-value [W/m²K]: | 2.20 |
Window glazing g-value [-]: | 1 |
Basement/Floor structure: | concrete slab |
Basement/Floor insulation location: | none |
Basement/Floor insulation material: | |
Basement/Floor thermal transmittance [W/m²K]: | 1.336 |
Roof structure: | plane - pre-fabricated |
Roof insulation location: | out |
Roof insulation material: | mineral |
Roof U-value [W/m²K]: | 0.600 |
Vehicle accessible roof covering [%]: | 0% |
Green roof covering [%]: | 0% |
ST roof covering [%]: | 0% |
PV roof covering [%]: | 0% |
SRR [%]: | |
Skylight U-value [W/m²K]: | 2.200 |
Skylight glazing g-value [-]: | 0.60 |
Technical room
Location: | vending area level |
---|---|
BMS lighting [Y/N]: | N |
BMS natural ventilation [Y/N]: | N |
BMS HVAC [Y/N]: | Y |
BMS refrigeration [Y/N]: | Y |
BMS solar thermal system [Y/N]: | N |
BMS electric storage [Y/N]: | N |
Ventilation specific power [Wh/m³]: | 0,833 - 0,97 |
Heat recovery thermal efficiency [%]: | 40 |
SPF heating [-]: | 0.84 |
SPF cooling [-]: | 2.70 |
Common areas
Installed lighting power density [W/m²]: | 15-20 |
---|---|
Installed electric equipment power density [W/m²]: | 10 |
Tenants
Installed lighting power density [W/m²]: | 38 |
---|---|
Installed electric equipment power density [W/m²]: | 4 |
Food store
Installed lighting power density [W/m²]: | 38 |
---|---|
Installed electric equipment power density [W/m²]: | 40 |
Primary energy consumption
Lighting [kWh/m²-y]: | 333 |
---|---|
Refrigeration [kWh/m²-y]: | |
Plug loads [kWh/m²-y]: | 113 |
HVAC [kWh/m²-y]: | 223 |
Tot. primary energy [kWh/m²-y]: | 669 |
Carbon emissions
Carbon emissions [tonCO2eq]: | 12350 |
---|
Inefficiencies
Envelope ineff.1: | outdated windows |
---|---|
Envelope ineff. 2: | Air leaks and cracks |
Envelope ineff. 3: | |
Lighting ineff.1: | Inefficient lamp technology and inefficient luminaires |
Lighting ineff. 2: | |
Lighting ineff. 3: | |
Refrigeration ineff. 1: | |
Refrigeration ineff. 2: | |
Refrigeration ineff. 3: | |
HVAC_general general ineff.: | |
HVAC_general general ineff.: | |
HVAC_heating heating ineff.: | |
HVAC_heating heating ineff.: | |
HVAC_cooling cooling ineff.: | |
HVAC_cooling cooling ineff.: | |
HVAC_ventilation ventilation ineff.: | |
HVAC_ventilation ventilation ineff.: |
Retrofit solution set I
Solution set I ID: | 6 |
---|---|
Primary energy consumption [kWh/m²-y]: | 301 |
Primary energy savings [%]: | 55% |
Carbon emissions tonCO2eq: | 8070 |
Carbon emission savings [%]: | 65% |
Investment cost [M€]: | 10.851 |
Operational energy cost [k€/year]: | 410 |
Pay-back time [years]: | 7 |
Net Present Value [M€]: | 17 |
Maintenance cost [k€/year]: | 110 |